söndag 30 november 2014

The test conditions

The test conditions for the heat pumps were taken from Table 20 in the standard, brine to water heat pump, average climate and low temperature application. The unit is assumed to be a fixed capacity unit with fixed outlet temperature. The heat pumps in the study where all tested in full load according to EN 14511. For the part load conditions the COP was calculated by using equation 12 in the standard. The test point used for the calculations was the 30°C/35°C point from EN 14511 laboratory data. The capacity and COP at Tbivalent and TOL is set to the maximum, while the COP for the delivered capacity at the different outdoor temperatures is calculated by using equations from the standard prEN14825. The default degradation factor where Cc=0.9 is used.